DF6000 - USER MANUAL
100
Zone Monitor Unit - MIU871
Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface mounting backbox.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according to the diagram below.
Notes:
No addressing of the interface is required. See control panel operation for details.
Standard Connections
Notes:
1. This unit can only be used with JSB FXN520 detector base and compatible detectors.
2. Only connect cable screen to its adjacent earth terminal.
3. The end of line resistor must always be fitted, even if the spur is unused.
4. Maximum spur length - See BS5839 Pt 1:2002 for aone coverage.
5. Maximum number of callpoints allowed is unlimited.
6. Detector zone end of line device is EOLM-1 (supplied)
7. Callpoint zone has end of line resistor
Section 5 - Appendix
Callpoints can be connected with
detectors on detector zone if preferred
Callpoint
zone
Detector
zone
Loop
In
Out
Analogue addressable loop
12K
EOLM-1
Out
In
Out
In
-
-
-
-
+
+
+
+
++++
----
EE E E