DF6000 - USER MANUAL
35
Output to Fire Alarm Protecting Equipment (option 7.10 EN54 Pt 2)
This output, which is fused and monitored using 6.8k end of line r
esistor is used for the transmission of
the fire signals to controls for automatic fire protecting equipment (e.g. Door release units etc).It operates
by providing 24 V output to an auxiliary device (e.g. relay).
It is current limited to 30 mA using a resettable polyswitch. Class change and test conditions do not
operate this output. If operated under a fire alarm condition, this output remains activated until the fire
alarm is reset. Ensure the polarity of the connections is observed at all times and end of line resistors (6k8
5%) are fitted for correct operation. All activated devices must be polarised.
Output to Fault Warning Routing Equipment (option 9.4.1c EN54 Pt 2)
This output, which is fused and monitored using 6.8k end of line resistor is used for the transmission of
fault signals to fault warning routing equipment This output is monitored using 6k8 end of line resistor and
it current limited to 30 mA.
Under normal conditions it operates by providing 24 V dc which can be connected directly to a 24 V
auxiliary device (relay). It is current limited to 30 mA. Under fault conditions or even if the DF6000 is
switched off, this output will switch to 0 V. Ensure the polarity of the connections is observed at all times
and end of line resistors (6k8 5%) are fitted for correct operation.
Auxiliary Relay (option not required by EN54)
This output is a volt free contact, which is protected by a polyswitch. It is rated at 24 V 1 Amp. If operated
under a fire alarm condition , this output will remain energised until the fire alarm is reset.
Auxiliary DC Output (option not defined by EN54)
A 24 V dc output is provided. This output is protected by a polyswitch. This output can be used to power
fire or fault auxiliary equipment. Please ensure that all equipments connected to this output will only draw
current when a fire condition exists.
WARNING: Do not exceed the rated output current
Mimic Output (option not required by EN54)
This RS485 output is used to send data to a mimic display or a repeater panel. The maximum distance is
2 km.
Section 1 - System Installation and Design